Products and Information
BSEN60893-3-4-PFCP201 B4 Phenolic Paper Laminate SRBP
Material Details
Grade: | B4. (Type: Paper Based Laminates - SRBP) |
---|---|
Description: | Phenolic Paper. Superior commercial grade |
Comments: | A high quality commercial grade for normal temperature and low-tension electrical applications such as flash barriers, secondary insulation in switchgear, jigs, fixtures and mechanical components. May be hot punched. |
Specifications: | BSEN60893-3-4-PFCP201 (Which supersedes BS2572 P1). The closest NEMA equivalent to this specification is NEMA X. |
Body Colour: | Brown |
Cover Colour: | Dark Brown |
Standard Finish: | Satin/Glossy |
Size: | 1220 x 1220 Thickness Range: 0.8 - 75.0 † |
Typical Applications
- Welding Jigs
- Terminal Boards and Tag Strips
- Precision Machined Parts
- Pipeline Insulation
- Mechanical Applications
- Low Voltage Insulation
- Jigs and Fixtures
- Coil Formers
General Properties
Property | Unit of measure | Typical Value |
---|---|---|
Density | g/cm3 |
1.35 |
Water Absorption | mg |
155 |
Flammability Category¥ | - |
FH1 |
¥ Where relevant, the flammability test method is used solely to control and monitor consistency of production. Under no conditions should the results be considered in relation to fire hazards under actual conditions of use.
Electrical Properties
Property | Unit of measure | Typical Value |
---|---|---|
IR (24hrs Water Immersed) | G Ω |
0.025 |
IR (Dry) | G Ω |
0.025 |
Electric Strength (Flat Rapid) | MV/m |
2 |
Breakdown Voltage (Edge Step by Step) | kV |
14.5 |
Tracking Index | V |
110 |
Mechanical Properties
Property | Unit of measure | Typical Value |
---|---|---|
Flexural Strength | MPa |
178 |
Tensile Strength | MPa |
120 |
Impact (Notched CHARPY) | kJ/m2 |
4.5 |
Thermal Properties
Property | Unit of measure | Typical Value |
---|---|---|
Thermal Rating Continuous | °C |
100 |
Thermal Rating Intermittent | °C |
120 |
Disclaimer: The above values are based upon routine test data and do not form the basis of a supply contract. These products may be used in a diverse range of applications and whilst every effort is made to ensure the information in this data sheet is accurate, it must be stressed that it is the user's responsibility to ensure suitability for the intended end use.